QUARTZ-RAY SERIES: Engineering Specifications
Heat Patterns
Mounting
Height
AREAS HEATED IN FEET
1 KW 1.75 KW 2.5 KW 3 & 4 KW
7 feet 8 x 10 8 x 11 8 x 12 8 x 13
8 feet 9.5 x 11.5 9.5 x 12 9.5 x 13 9.5 x 14.5
9 feet 10.5 x 12.5 10.5 x 13 10.5 x 14 10.5 x 15.5
10 feet .................. 11.5 x 14.5 11.5 x 15.5 11.5 x 16.5
11 feet .................. 12.5 x 15 12.5 x 16 12.5 x 17.5
12 feet .................. .................. 14 x 18 14 x 19
13 feet .................. .................. 15 x 18.9 15 x 20
14 feet .................. .................. .................. 16 x 21
15 feet .................. .................. .................. 17.5 x 22.5

Watts Density at Floor Level
Mounting
Height
DENSITY IN WATTS
1 KW 1.75 KW 2.5 KW 3 KW 4 KW
7 feet

12.4

20.0 26.5 28.8 38.4
8 feet 9.2 16.1 20.1 22.0 29.4
9 feet 7.6 13.4 16.8 18.6 24.9
10 feet ............... 11.1 14.5 16.0 21.6
11 feet ............... 9.3 12.5 14.0 18.7
12 feet ............... ............... 10.0 11.2 15.0
13 feet ............... ............... 8.8 10.0 13.3
14 feet ............... ............... ............... 8.9 11.9
15 feet ............... ............... ............... ............... 10.9

Standard Ratings and Sizes
MODELS Overall
Length
Heated
Length
VOLTS WATTS AMP
*B AH-18-A-05 18" 13" 120 500 4.18
*B AH-25-A-10 25" 20" 120 1000 8.32
*B AH-25-B-10 25" 20" 208 1000 4.8
*B AH-25-C-10 25" 20" 240 1000 4.18
*B AH-35-A-17 35" 30" 120 1750 13.8
*B AH-35-B-17 35" 30" 208 1750 8.32
*B AH-35-C-17 35" 30" 240 1750 7.1
*B AH-45-B-25 45" 40" 208 2500 11.7
*B AH-45-C-25 45" 40" 240 2500 10.0
*B AH-60-B-30 60" 55" 208 3000 13.9
*B AH-60-C-30 60" 55" 240 3000 12.0
*B AH-60-C-40 60" 55" 240 4000 16.3
*B AH-60-D-40 60" 55" 575 4000 6.95
*Approved for brooder use.
All models require single phase supply voltage.

Estimating Required Loadings
Type of Building Watts Required per
Square Foot at
Floor Level
Insulated Building
Uninsulated
Outdoor Sheltered
Outdoor Unsheltered
10
16
25 - 30
30 - 45
The above figures are for a design of 0 degrees F.
Add the following watts per square foot for the following temperatures below zero.

-5       Add 0.75 watts per square foot.
-10      Add 1.50 watts per square foot.
-15      Add 2.25 watts per square foot.
-20      Add 3.00 watts per square foot.

IMPORTANT: The above table is designed for a mounting height of 9 feet above floor level. For higher mountings add 10% of the total watts for each foot above 9 feet. For lower than 9 feet mountings deduct 10% of the total watts for each foot below 9 feet.